Since 23 January 2023, the Fire Safety (England) Regulations 2022 have required the responsible person for a block of flats over 11 metres to try to check every flat entrance fire door at least once every 12 months.[1] Nearly three years on, the check is rarely the hard part. Getting through the front door often is.
This article sets out what the law asks, what a check involves, and what to record when a resident will not give access.
Which buildings are covered
Regulation 10 applies to any building with two or more flats and common parts that residents would use to escape in a fire. In all of them, the responsible person must tell residents three things: fire doors should be kept shut when not in use, self-closing devices should not be tampered with, and faults or damage should be reported straight away. New residents must be told when they move in, and everyone must be reminded at least once every 12 months.
The routine checks apply only where the top storey is more than 11 metres above ground level, which the government's guidance describes as typically a building of more than four storeys.[2] In those blocks:
• fire doors in communal areas must be checked at least every three months
• flat entrance doors must be checked at least every 12 months, on a "best endeavours" basis
• both checks must include making sure the self-closing devices work.
The duties fall on freeholders and others in control of the building, such as managing agents. A breach is a criminal offence if it puts residents, staff or visitors at risk of death or serious injury.
What a check involves
The guidance, revised in August 2025, says the checks "should be simple and basic". They are visual, need no tools, and can be carried out by caretakers, managing agents, housing officers or maintenance staff with appropriate instruction.
For each flat entrance door, the guidance lists what to look for:
• a replacement door that may not be fire-resisting
• a letterbox jammed open, or an unsuitable one added later
• damage to the door, frame or surrounding wall, including holes left by old locks
• damaged or unsuitable glazing
• loose or missing hinge screws and other faulty ironmongery
• intumescent strips and smoke seals, where fitted, that are damaged or painted over
• gaps between door and frame larger than the 4mm the guidance calls the industry standard
• a self-closing device that does not work.
For the closer, open the door fully and let go, then open it to about 15 degrees and let go. Both times it should close fully into the frame, overcoming the latch.
The revised guidance also corrects a costly misunderstanding. The absence of intumescent strips, smoke seals or any certification does not, on its own, make an existing door unfit for purpose. In most cases, a door that met the standard when the block was built or the door was made will still do its job, provided it is undamaged and the gaps are not too large. Whether a type of door suits its location is a matter for the fire risk assessment under the Regulatory Reform (Fire Safety) Order 2005 (the Fire Safety Order), not for these routine checks.[3]
The access problem
A flat entrance door has to be seen from both sides, so the person checking needs to get into the flat. Residents work, travel, sublet, or simply say no.
The law does not demand the impossible. It demands best endeavours and a record. Regulation 10 says the responsible person must keep a record of the steps taken to check flat entrance doors, including, where access was not granted, the steps taken to try to gain it.
In practice, a sound record for a door that could not be checked shows:
• the date and method of each attempt: letter, email, phone call or knock at the door
• the appointment times offered, ideally more than one
• any reply received, and what it said
• what was seen from the communal side, such as the closer arm, visible damage and the corridor-side gaps, recorded as a partial check rather than a full one
• the next step planned.
The guidance suggests offering a range of times and notes that, outside very small blocks, one visit is unlikely to cover every door. Where a resident persistently refuses, it says legal action may ultimately need to be considered. Many leases give a right of entry on notice for inspection, so the lease is worth reading first.
What a good record looks like
For each door checked, a clear record includes:
• the flat number and door location
• the date, and the name of the person who carried out the check
• the result for each item on the checklist
• photographs of any defects
• who was told about each defect, and when it was put right.
The guidance includes a sample checklist and confirms that electronic records are acceptable.
When a check finds a defect
The guidance says any repair or replacement must be carried out by a competent contractor as soon as reasonably practicable. Where a resident has fitted a new door, the resident must show it is fire-resisting and provide its technical information.
A failed check does not automatically mean a new door. Whether a defective door is repaired, upgraded or replaced is a decision for the fire risk assessor, who weighs that particular doorset against the whole building before anything is replaced. The responsible person makes the final call.
Checks are not inspections
Routine checks will find most everyday defects, but the guidance says they "are not a substitute for periodic assessment of fire doors by fire safety specialists", for example on a sample basis during a fire risk assessment. The yearly check is the legal minimum that keeps doors working in between.
References
1. The Fire Safety (England) Regulations 2022 (SI 2022/547), regulation 10. legislation.gov.uk/uksi/2022/547/regulation/10/made
2. Ministry of Housing, Communities and Local Government and Home Office, "Fire Safety (England) Regulations 2022: fire door guidance", revised 8 August 2025. gov.uk/government/publications/fire-safety-england-regulations-2022-fire-door-guidance
3. Regulatory Reform (Fire Safety) Order 2005 (SI 2005/1541).